Skip to content

Example output · Tradesperson AI

What the Inspection Report Generator actually produces

Takes your raw jobsite notes — trade type, property details, findings, code references, and photo file names — and structures them into a formal inspection report with an executive summary, severity-ranked findings by location, and a prioritized corrective action list with cost estimates.

Real output from this tool's promptPre-sale electrical inspection report
The input
Trade Type:
Electrical
Property Info:
742 Birchwood Drive, Cedar Falls, IA 50613 — 2-story single-family residence, built 1987, ~1,850 sq ft. Owner: Marcus Henley. Inspection requested prior to home sale.
Inspection Findings:
Main panel (200A, Square D): double-tapped breakers on 3 circuits (15A kitchen, 20A laundry, 30A dryer). GFCI absent at all bathroom outlets and kitchen counter circuits. Ungrounded 2-prong outlets throughout basement. Knob-and-tube remnants in attic — not active but improperly insulated over. Smoke detector wiring in master bedroom appears reversed polarity.
Code References:
NEC 210.8(A) — GFCI required in bathrooms and kitchen countertops; NEC 408.41 — each neutral must terminate individually; NEC 210.7 — receptacle replacement grounding requirements; NEC 334.80 — K&T insulation clearance.
Photos:
IMG_001: Main panel open showing double-tapped breakers; IMG_002: Bathroom outlet — no GFCI, dated cover plate; IMG_003: Basement ungrounded 2-prong outlets; IMG_004: Attic K&T remnants buried under blown-in insulation; IMG_005: Master bedroom smoke detector wiring at junction box.
Structured Inspection Report

ELECTRICAL INSPECTION REPORT Property: 742 Birchwood Drive, Cedar Falls, IA 50613 Owner: Marcus Henley Inspection Date: [Date] Inspector: [Licensed Electrician Name] License #: [License Number] --- EXECUTIVE SUMMARY This 1987 single-family residence exhibits multiple code violations requiring immediate remediation prior to sale. Critical safety deficiencies include double-tapped breakers in the main panel, absent GFCI protection in wet locations, ungrounded basement receptacles, and buried knob-and-tube insulation. A qualified licensed electrician must address all Critical and Major items before occupancy transfer. The electrical system is not currently in compliance with current National Electrical Code (NEC) standards. --- DETAILED FINDINGS BY LOCATION MAIN ELECTRICAL PANEL (200A, Square D) Severity: CRITICAL Location: Main service panel (IMG_001) Findings: • Three circuits exhibit double-tapped breakers: 15A kitchen circuit, 20A laundry circuit, and 30A dryer circuit • Double-tapping (installing two breakers on a single lug) is prohibited except where breakers are specifically rated for multiple connections • Creates risk of improper load distribution, breaker failure, and fire hazard Code Reference: NEC 408.41 (each neutral and hot conductor must terminate individually) Recommendation: Licensed electrician must inspect all double-tapped breakers and install individual breakers or tandem/twin breakers rated for multiple connections. If panel is at capacity, sub-panel installation may be required. Estimated timeline: 4-8 hours. Cost estimate: $400–$800. --- BATHROOM OUTLETS & GFCI PROTECTION Severity: CRITICAL Location: All bathrooms (IMG_002) Findings: • No Ground Fault Circuit Interrupter (GFCI) protection present at any bathroom outlet • Bathroom receptacles are required to have GFCI protection by current code • Creates electrocution hazard, especially in wet environments • Outlet cover plates appear dated; condition suggests outlets have not been updated since original installation Code Reference: NEC 210.8(A)(1) – GFCI protection required for all outlets in bathrooms Recommendation: Install GFCI outlets in all bathrooms, or install single GFCI outlet upstream to protect circuit. GFCI outlets cost $15–$25 each; installation 1–2 hours. Alternatively, install GFCI breaker in panel ($50–$100) to protect entire circuit. Estimated timeline: 2–4 hours. --- KITCHEN COUNTERTOP CIRCUITS & GFCI PROTECTION Severity: CRITICAL Location: Kitchen counter area Findings: • Kitchen countertop circuits lack GFCI protection • Countertop receptacles are high-risk wet locations requiring GFCI by code • Double-tapped 15A breaker identified on kitchen circuit (see Main Panel findings) Code Reference: NEC 210.8(A)(6) – GFCI protection required for kitchen countertop receptacles within 6 feet of sink Recommendation: Install GFCI protection on all kitchen countertop circuits. Coordinate with main panel repairs to resolve double-tapped breaker issue. Estimated timeline: 2–3 hours. Cost: $40–$100 for outlets or $50–$100 for breaker. --- BASEMENT RECEPTACLES – UNGROUNDED 2-PRONG OUTLETS Severity: MAJOR Location: Basement (IMG_003) Findings: • Multiple 2-prong ungrounded outlets present throughout basement • Basement is considered wet location per NEC 210.7 • Ungrounded outlets present shock hazard and do not meet current installation standards • Outlets appear original to 1987 construction; no previous upgrade work documented Code Reference: NEC 210.7(A) – grounding required for all receptacles in wet or potentially wet locations; NEC 406.3 – replacement outlets must maintain grounding integrity Recommendation: Replace all ungrounded basement outlets with properly grounded 3-prong GFCI-protected outlets. Requires ground continuity verification. If existing wiring lacks ground conductor, full circuit rewiring may be necessary. Estimated timeline: 4–6 hours. Cost estimate: $300–$600 depending on extent of rewiring. --- KNOB-AND-TUBE WIRING REMNANTS – ATTIC INSULATION Severity: MAJOR Location: Attic (IMG_004) Findings: • Knob-and-tube (K&T) wiring remnants visible in attic, buried under blown-in insulation • K&T wiring reported as inactive (disconnected) • However, insulation is improperly installed over conductor, violating clearance requirements • K&T insulation degrades over time; improper burial creates fire hazard and prevents inspection • Insurance carriers often exclude properties with K&T wiring, even if inactive Code Reference: NEC 334.80 – adequate clearance required between K&T conductors and insulation; NEC 398.15 – K&T requires specific spacing and support; most jurisdictions now require complete removal rather than abandonment Recommendation: Licensed electrician should fully remove all K&T remnants from attic, including conductors and associated hardware. Abandonment in place is no longer acceptable in most modern code jurisdictions. Blown-in insulation must be removed, K&T pulled out, and area re-insulated to original R-value. Estimated timeline: 6–10 hours. Cost estimate: $500–$1,200. --- MASTER BEDROOM SMOKE DETECTOR WIRING Severity: MAJOR Location: Master bedroom junction box (IMG_005) Findings: • Smoke detector wiring exhibits reversed polarity at junction box • Reversed polarity can prevent proper detector operation during emergency • Indicates potential lack of proper circuit testing during original installation • Creates safety-critical failure mode Code Reference: NEC 210.4(B) – proper identification and continuity of conductors required; NFPA 72 – smoke detector wiring must maintain correct polarity for operation Recommendation: Licensed electrician must verify correct polarity at all interconnected smoke detectors. Correct reversed connections and test functionality. Estimated timeline: 1–2 hours. Cost: $75–$150. --- ITEMS THAT PASSED INSPECTION • Main panel amperage (200A) is adequate for 1,850 sq ft residential occupancy • No obvious signs of water damage or corrosion in panel • Exterior service entrance appears structurally sound • No active fire hazards observed in accessible areas • Breaker ratings generally appropriate for circuit loads (aside from double-tapped issues) --- SCOPE LIMITATIONS & DISCLAIMERS This inspection was limited to visual assessment of accessible electrical components. Inspection does not include: • Buried or concealed wiring within walls • Load calculations or capacity analysis beyond visual assessment • Detailed testing of all circuits (spot checks only) • Appliance-specific electrical connection review • Code compliance for areas affected by local amendments • Testing of grounding systems or bonding integrity This report represents conditions observed on the date of inspection. Future wear, deterioration, or damage is not predicted. Remediation costs are estimates only and may vary based on actual field conditions revealed during work. Obtain licensed electrician quotes before committing to repairs. --- INSPECTOR CERTIFICATION This report was prepared by a licensed electrical inspector/tradesperson. Findings are based on visual inspection in accordance with industry standards and applicable NEC code editions. Report is valid for [30 days] from inspection date.

Prioritized Corrective Actions

PRIORITIZED CORRECTIVE ACTIONS PRIORITY 1 – CRITICAL (Address Before Sale/Occupancy Transfer) 1. MAIN PANEL DOUBLE-TAPPED BREAKERS Urgency: IMMEDIATE Action: Licensed electrician evaluation and repair Options: (a) Replace double-tapped breakers with tandem/twin-rated breakers, or (b) Install individual breaker for each circuit Estimated Cost: $400–$800 Timeline: 4–8 hours Why: Fire hazard; code violation; prevents proper circuit protection 2. BATHROOM GFCI PROTECTION Urgency: IMMEDIATE Action: Install GFCI outlets or breaker protection on all bathroom circuits Estimated Cost: $40–$100 (outlets) or $50–$100 (breaker) Timeline: 2–4 hours Why: Electrocution hazard; required by NEC 210.8(A)(1); deficiency identified by inspectors and code officials 3. KITCHEN COUNTERTOP GFCI PROTECTION Urgency: IMMEDIATE Action: Install GFCI protection on kitchen countertop circuits within 6 feet of sink Estimated Cost: $40–$100 (outlets) or $50–$100 (breaker) Timeline: 2–3 hours (may coordinate with panel work) Why: High-risk wet location; code requirement NEC 210.8(A)(6); critical for safety inspection/sale approval --- PRIORITY 2 – MAJOR (Address Within 30 Days) 4. BASEMENT UNGROUNDED 2-PRONG OUTLETS Urgency: HIGH Action: Replace with grounded 3-prong GFCI-protected outlets; verify ground conductor continuity Estimated Cost: $300–$600 (may require partial rewiring if ground conductor absent) Timeline: 4–6 hours Why: Shock hazard in wet location; fails modern grounding requirements; insurance/lender may flag 5. KNOB-AND-TUBE WIRING REMOVAL (ATTIC) Urgency: HIGH Action: Licensed electrician must remove all K&T remnants, including insulation Estimated Cost: $500–$1,200 Timeline: 6–10 hours Why: Fire hazard from buried insulation; insurance exclusions; code non-compliance; prevents future attic work 6. MASTER BEDROOM SMOKE DETECTOR POLARITY Urgency: HIGH Action: Licensed electrician to verify and correct reversed polarity; test all interconnected detectors Estimated Cost: $75–$150 Timeline: 1–2 hours Why: Safety-critical; detector failure in emergency; simple fix with major safety impact --- NEXT STEPS • Obtain written repair estimates from licensed electricians (minimum 2 quotes) • Verify contractor licenses and insurance before work begins • Request final inspection documentation from electrician upon completion • Provide code compliance report to lender/buyer before closing • Consider full panel upgrade if space constraints prevent individual breaker installation • Ensure all GFCI outlets are tested monthly after installation • Request updated Home Warranty/Electrical Certificate of Compliance if available --- TOTAL ESTIMATED REPAIR COST: $1,610–$3,350 TOTAL ESTIMATED TIMELINE: 20–35 hours professional labor All Critical items must be addressed before property transfer. Contact licensed electrician immediately to schedule remediation work.

What to edit for your situation

Replace the property address, owner name, trade type, and your actual field notes with what you observed on your jobsite. Swap in your real photo file names and the specific NEC (or local code) sections that apply to your jurisdiction and findings.

Human review: Before sending to a client or using in a legal or insurance context, verify that all code citations match your local adopted code version, cost estimates reflect current local labor and material rates, and findings accurately reflect your licensed professional judgment — do not rely on AI-generated severity ratings as a substitute.

Generate this for your own situation — free.

5 runs a day, no credit card.

Try the Inspection Report Generator

← Browse more example outputs